Tytan II Main protection

D02 – Fuse switch disconnector with supervisory relay

Fool-proof rated voltage with full coding
The TYTAN® colour coding system is designed for all amperages. It also caters to the new amperages of 13, 32 and 40 A.

  • integrated flashing indicator (OEFI)
  • safety switch
  • codeable for ALL amperages
  • sealable
  • lockable

Technical data

ClassificationFuse switch disconnector
NormIEC 60947-3, IEC 60269-3
Suitable for fuses

D01: 1, 2, 4, 6, 10, 13, 16;
D02: 20, 25, 32, 35, 40, 50, 63AgL, gG, aM
Fire classification / Track resistanceUI94 / V0, heating wire resistance 960°C / CTI 600
Protection / Voltage contact protectionIP20 / finger and back of hand proof
Rate operational voltage Ue 
-AC400V
-DC1-pole 110V, 2-pole 220V
Rated operational current Ie63A
Over voltage category ­/ degree of pollutionIV/3 (DIN VDE 0110)
Rated impulse withstand voltage Uimp6000V
Type of terminationsStainless steel cage clamp 1,5...35mm ; MD 4Nm, pozidriv
Rated short circuit making capacity Icm50kAeff
Utilization categoryAC 22B, DC 21B

 

Dimensions

Item-No.Component width a in mm
10 275154
10 275281
10 2753108
10 274181
10 2743135
10 271154
10 271281
10 2713108

 

Item
Item-No.
Component width a in mmkg/Pc.Packaging
1-pole; with fuse monitoring 60-230/400V AC10 2751540,186
2-1-pole; with fuse monitoring 60-230/400V AC10 2752810,294
3-1-pole; with fuse monitoring 60-230/400V AC10 27531080,413
1-pole+N; with fuse monitoring 60-230/400V AC (N pre-/post lagging phase)10 2741810,314
3-pole+N; with fuse monitoring 60-230/400V AC (N pre-/post lagging phase)10 27431350,542
1-pole; with fuse monitoring 60-110V DC10 2751   0,186
2-pole; with fuse monitoring 60-220V DC10 2752   0,294
1-pole; with fuse monitoring 24-60V AC/DC10 2711540,186
2-pole; with fuse monitoring 24-60V AC/DC10 2712810,294
3-pole; with fuse monitoring 24-60V AC/DC10 27131080,413